The further devel­opment of our special flanges is combined in the VP flange, which is equipped with a corrosion-free, fiber-reinforced plastic backing flange drilled to DIN EN 1092 PN 10. Slotted holes in the collar allow easier assembly and alignment of the flange connection. The spring effect of the flange integrated into the design, which ensures permanent bolt preten­sioning, is a particular highlight. Its low weight in particular reduces instal­lation work and project costs.

Technical data

Technische Zeichnung Steckmuffe Doppelsteckkupplung

Complete data sheet

Tender text

PE100 fittings with tensile plug-in connection REINOGRIP system Generalprelim­inary remarks The fittings to be offered must be made of material in accor­dance with the PE100+ Associ­ation and comply with DIN EN 12201 in terms of dimen­sions, toler­ances and quality require­ments. Proof of production on the basis of a quality assurance system in accor­dance with DIN EN ISO 9001 must be provided. A certificate in accor­dance with DIN EN 10204 must be provided by the manufac­turer for all molded parts. Alter­na­tively, the body of the molded part must be manufac­tured from a single piece of homoge­neous semi-finished material using the injection molding process, even for more complex struc­tures, in order to ensure the required reinforcement and thus high stability of the molded part. Semi-finished products made from winding rod or other subse­quently applied reinforce­ments are not permitted. The tension-resistant plug connec­tions must have grip elements, each with at least 5 grip teeth made of high-strength plastic, which are arranged on spring-loaded holders.
An elastomer ring must ensure that the grip is self-activating.
An elastomer profile ring must be fitted at the inlet of the plug connection as a wiper to prevent the ingress of dirt.
A pressure-tight System 3S lip seal in drinking water quality must be installed as a media seal.
Spigot ends on the fittings must be long in order to be able to carry out both plugging and HE butt welding or HW welding.
Flange connection dimen­sions must be designed in accor­dance with DIN EN 1092–1.
Depending on the type of mating flange, flange connec­tions must be designed either as a loose flange connection or as a fixed flange connection (with the same nominal width). The backing flanges must be made of corrosion-free, fiber-reinforced plastic. The collar and flange must interlock positively at their connecting surfaces and the flange must also support the collar from the outside to counteract deformation.
This ensures that the flange connection can withstand full pressure in accor­dance with the pipe dimensions.
The backing flange is captively connected to the welding neck.
The use of a profile seal for flat-sealing collars is recom­mended if no other seal is available in the system.

  • Read more

    1. PE100 double coupler, pull-resistant according to DVGW, pressure class-compatible, with EPDM lip seal and dirt-repellent profile ring, for PE100 pipe of the size

    DN/OD [d1] …

    SDR …

    Operating pressure … bar

    1. PE100 bend 1 x d, with push-fit coupling on both sides, pull-resistant according to DVGW, pressure class-compatible, with EPDM lip seal and dirt-repellent profile ring, for PE100 pipe of the size

    DN/OD [d1] …

    SDR …

    … degrees

    Operating pressure … bar

    1. PE100 bend 1 x d, with push-fit coupler on one side, pull-resistant according to DVGW, pressure class-compatible, with EPDM lip seal and dirt-repellent profile ring, for PE100 pipe of the size

    DN/OD [d1] …

    SDR …

    … degrees

    Operating pressure … bar

    1. PE100 tee, with all-round push-fit coupling, pull-resistant according to DVGW, pressure class-compatible, with EPDM lip seal and dirt-repellent profile ring, for PE100 pipe of the size

    DN/OD1 [d1] …

    DN/OD2 [d2] …

    SDR …

    Operating pressure … bar

    1. PE100 tee with HP flange outlet, with push-fit couplers in the run pipe, pull-resistant according to DVGW, pressure class-compatible, with EPDM lip seal and dirt-repellent profile ring, for PE100 pipe of the size

    DN/OD [d1] …

    SDR …

    DN …

    PN … drilled

    Operating pressure … bar

    1. PE100 concentric reducer, with push-fit coupling on both sides, pull-resistant according to DVGW, pressure class-compatible, with EPDM lip seal and dirt-repellent profile ring, for PE100 pipe of the size

    DN/OD1 [d1] …

    DN/OD2 [d2] …

    SDR …

    Operating pressure … bar

  • Read more

    7. PE100 concentric reducer, with coupler on one side, pull-resistant according to DVGW, pressure class-compatible, with EPDM lip seal and dirt-repellent profile ring, second side long for HW welding , for PE100 pipe of the size

    DN/OD8 [d1] …

    DN/OD9 [d2] …

    SDR …

    Operating pressure … bar

    8. PE100 repair coupler, pull-resistant according to DVGW, pressure class-compatible, with EPDM lip seal and bolt preload for secure fixing, for pipes of the size

    Material 1: □ PE100 □ PVC □ PP

    DN/OD1 [d1] …

    SDR …

    Material 2: □ PE100 □ PVC □ PP

    DN/OD1 [d1] …

    SDR …

    Operating pressure … bar

    9. PE100 push-fit socket, consisting of push-fit coupler, pull-resistant according to DVGW, pressure class-compatible, with EPDM lip seal and dirt-repellent profile ring, and HP flange for PE100 pipe of the size

    DN/OD1 [d1] …

    SDR …

    DN …

    PN …

    Operating pressure … bar

    10. PE100 telescope repair set, with push-fit coupling on both sides, pull-resistant according to DVGW, pressure class-compatible, with EPDM lip seal and dirt-repellent profile ring, for pipes of the size

    Material 1: □ PE100 □ PVC □ PP

    DN/OD1 [d1] …

    SDR …

    Material 2: □ PE100 □ PVC □ PP

    DN/OD1 [d1] …

    SDR …

    Operating pressure … bar

    11. PE100 duckfoot bend for connection to hydrant, reinforced design, with push-fit coupler, pull-resistant according to DVGW, pressure class-compatible, with EPDM lip seal and dirt-repellent profile ring, with adapter for hydrants with bayonet spigot, for pipes of the size

    DN/OD1 [d1] …

    SDR …

    Operating pressure … bar

    12. PE100 hydrant end piece for service line connection, reinforced design, with push-fit coupler, pull-resistant according to DVGW, pressure class-compatible, with EPDM lip seal and dirt-repellent profile ring, with adapter for hydrants with bayonet spigot, for pipes of the size

    DN/OD1 [d1] …

    SDR …

    DN/OD3 [d3] …

    SDR …

    Operating pressure … bar

    13. PE100 tee for connection to hydrant, reinforced design, with push-fit coupler on both sides, pull-resistant according to DVGW, pressure class-compatible, with EPDM lip seal and dirt-repellent profile ring, with adapter for hydrants with bayonet spigot, for pipes of the size

    DN/OD1 [d1] …

    SDR …

    Operating pressure … bar

    14. PE100 cross for connection to hydrant, reinforced design, with all-round push-fit coupling„ pull-resistant according to DVGW, pressure class-compatible, with EPDM lip seal and dirt-repellent profile ring, with adapter for hydrants with bayonet spigot, for pipes of the size

    DN/OD1 [d1] …

    SDR …

    Operating pressure … bar

  • Read more

      1. PE100 X‑cross for connection to hydrant, reinforced design, with all-round push-fit coupling„ pull-resistant according to DVGW, pressure class-compatible, with EPDM lip seal and dirt-repellent profile ring, with adapter for hydrants with bayonet spigot, for pipes of the size

      DN/OD1 [d1] …

      SDR …

      Operating pressure … bar

      1. PE100 duckfoot bend for connection to hydrant, reinforced design, with push-fit coupler, pull-resistant according to DVGW, pressure class-compatible, with EPDM lip seal and dirt-repellent profile ring, with special flange connection (VP flange) of the same nominal diameter with fibre-reinforced backing flange at outlet, drilled according to DIN EN 1092–1, with spring effect for continuous bolt preload, for pipes of the size

      DN/OD1 [d1] …

      SDR …

      DN …

      Operating pressure … bar

      1. PE100 hydrant end piece for service line connection, reinforced design,with push-fit coupler, pull-resistant according to DVGW, pressure class-compatible, with EPDM lip seal and dirt-repellent profile ring, with special flange connection (VP flange) of the same nominal diameter with a fibre-reinforced backing flange at the outlet, drilled according to DIN EN 1092–1, with spring effect for continuous bolt preload, for pipes of the sizes

      DN/OD1 [d1] …

      SDR …

      DN …

      DN/OD3 [d3] …

      SDR …

      Operating pressure … bar

      1. PE100 tee for connection to hydrant, reinforced design, with push-fit coupler on both sides, pull-resistant according to DVGW, pressure class-compatible, with EPDM lip seal and dirt-repellent profile ring, with special flange connection (VP flange) of the same nominal diameter with fibre-reinforced backing flange at outlet, drilled according to DIN EN 1092–1, with spring effect for continuous bolt preload, for pipes of the sizes

      DN/OD1 [d1] …

      SDR …

      DN …

      Operating pressure … bar

      1. PE100 cross for connection to hydrant, reinforced design, with all-round push-fit coupling, pull-resistant according to DVGW, pressure class-compatible, with EPDM lip seal and dirt-repellent profile ring, with special flange connection (VP flange) of the same nominal diameter with fibre-reinforced backing flange at outlet, drilled according to DIN EN 1092–1, with spring effect for continuous bolt preload, for pipes of the sizes

      DN/OD1 [d1] …

      SDR …

      DN …

      Operating pressure … bar

      1. PE100 X‑cross for connection to hydrant, reinforced design, with all-round push-fit coupling, pull-resistant according to DVGW, pressure class-compatible, with EPDM lip seal and dirt-repellent profile ring, with special flange connection (VP flange) of the same nominal diameter with fibre-reinforced backing flange at outlet, drilled according to DIN EN 1092–1, with spring effect for continuous bolt preload, for pipes of the sizes

      DN/OD1 [d1] …

      SDR …

      DN …

      Operating pressure … bar

    Proof of delivery:
    Reinert-Ritz GmbH
    Ernst-Heinkel-Straße 2
    48531 Nordhorn
    Tel.: +49 5921 8347–0
    Fax: +49 5921 8347–25
    www.reinert-ritz.de
    Email: contact@reinert-ritz.com

Downloads

REINOGRIP double plug-in coupling data sheet

Instal­lation instructions

REINOGRIP brochure

REINOGRIP product catalog

No root ingrowth with REINOGRIP