Service line connection distributor

The flexible manifold for house connec­tions at the hydrant connection

The house connection manifold offers the option of making up to four house connec­tions to a flange connection to the hydrant if required. This can be done both during construction progress and retro­spec­tively. Different pipe diameters can be realized at the house connection manifold. The house connection manifold can also be used in a cast iron pipe system.

Technical data

Technische Zeichnung Hausanschlussverteiler

Complete data sheet

Tender text

PE100 hydrant fittings (T‑cross piece, X‑cross piece, house connection manifold)

General prelim­inary remarks

The fittings to be offered must be supplied as a set consisting of a welding neck and a backing flange adapted to the dimension. The welding neck collars must be made of material in accor­dance with the PE100+ Associ­ation and comply with DIN EN 12201 and DIN EN 1555 in terms of dimen­sions, toler­ances and quality require­ments. The backing flanges must be made of corrosion-free, fiber-reinforced plastic. Proof of production on the basis of a quality assurance system in accor­dance with DIN EN ISO 9001 must be provided. For all

The molded parts to be offered must be made of material in accor­dance with the PE100+ Associ­ation and comply with DIN EN 12201 with regard to dimen­sions, toler­ances and quality require­ments. Proof of production on the basis of a quality assurance system in accor­dance with DIN EN ISO 9001 must be provided. A certificate in accor­dance with DIN EN 10204 must be provided by the manufac­turer for all molded parts. The body of the molded part must be made from a single piece of homoge­neous semi-finished product in order to ensure the required reinforcement and thus high stability of the molded part. Semi-finished products made from winding rod or other subse­quently applied reinforce­ments are not permitted.

The spigot ends must be long in order to be able to carry out both HE butt welding and HW welding.

The flange connec­tions must be designed with the same nominal diameter as DN 80 or DN 100 in accor­dance with DIN EN 1092–1 and have an outwardly reinforced weld seam area designed for the load of the hydrant; DN 80 -> 110 mm outside diameter and DN 100 -> 135 mm outside diameter.

The backing flange is made of corrosion-free, fiber-reinforced plastic, supports the PE collar from the outside and has a disc spring function that maintains the preload after tight­ening the screws.

Optionally available versions: Flange with O‑ring seal, holder for spigot end or Württem­berger system at the outlet

fittings or steel flanges, for example.

  • Read more

    Standards/guidelines
    DIN EN 12201, DIN EN 1092–1, DVS 2207, DVS 2210, DIN EN 10204, DIN EN ISO 9001, DIN EN ISO 50001, DVGW W 400–2, DVGW GW 335

    Approvals/certificates

    Inspection certificate 3.1 according to DIN EN ISO 10204 on the semi-finished product of the processed raw material with indication of MFR and OIT; only PE100 material according to PE100+ Association

    Manufac­turer certified according to ISO 9001:2015 and ISO 50001:2011

    Manufac­turer:
    Reinert-Ritz GmbH or equal

    Perfor­mance specification:

    1. PE100 T‑cross piece for hydrant connection, reinforced version, with special flange connection (VP flange) of the same nominal diameter with fibre-reinforced backing flange at the outlet, drilled to DIN EN 1092–1, with spring action for continuous bolt preload, long welding ends for HW welding, d1 … / DN … SDR …
      PE100 X‑cross piece for hydrant connection, reinforced version, with special flange connection (VP flange) of the same nominal diameter with fibre-reinforced backing flange at the outlet, drilled to DIN EN 1092–1, with spring action for continuous bolt preten­sioning, long welding ends for HW welding, d1 … / DN … SDR …
      PE100 service connection manifold with four connection options, reinforced version with extra-long service connection spigot and three blanking plugs with EPDM O‑ring, suitably drilled to DIN EN 1092–1, sealing surface with EPDM O‑ring, n x d1 … / DN … SDR … | n x d3 … / DN … SDR …

    Proof of delivery:
    Reinert-Ritz GmbH
    Ernst-Heinkel-Straße 2
    48531 Nordhorn
    Tel.: +49 5921 8347–0
    Fax: +49 5921 8347–25
    www.reinert-ritz.de
    Email: contact@reinert-ritz.com

Downloads

Hydrant connection manifold data sheet

Hydrant program

RR product catalog

Molded parts in practice